Abstract A hospital warm water system was monitored for the presence and distribution of legionellae. Subtyping of ten selected Legionella pneumophila isolates, originating from four different sites in the system by using serogroup specific antisera in an indirect immunofluorescence test, revealed that nine of the ten isolates belonged to serogroup 6, while the remaining one was serogroup 10. Two monoclonal antibodies (mAbs) specific for a subgroup of serogroup 6 strains were further used for characterization. None of the strains reacted with these mAbs. Genome analysis by elaborating NotI profiles using the pulsed field gel electrophoresis (PFGE) technique revealed that nearly all serogroup 6 isolates derived from different sites, including a new building connected by a ring pipe, were identical according to restriction fragment patterns. The patterns were distinguishable from those of the two L. pneumophila serogroup 6 reference strains, and from that of the L. pneumophila serogroup 10 isolate. These data argue for a relatively homogeneous L. pneumophila serogroup 6 population in the entire water system.