Description / Table of Contents:
Contents In the transient analysis of turboalternators, the reactancesX d ′ andX q ′ are assumed to be constants. In saturated machines, however, these reactances are functions of the pre-transient load of the alternator. For more exact analyses saturated reactances should be used. Using an approximate solution of the quasi-Poissonian differential equation the field leakage reactance and the transient reactances are calculated from flux linkages. As an example a Westinghouse alternator with the following nameplate data has been analyzed: 200 MVA, 15 kV, 50 Hz and 4 poles. The results of the numerical analysis has been compared with those of conventional methods of calculation.
Notes:
Übersicht Bei transienten Untersuchungen von Turbogeneratoren werden die ReaktanzenX d ′ undX q ′ als konstant angenommen. In gesättigten Maschinen sind jedoch diese Reaktanzen von der Vorbelastung abhängig. Für genauere Studien sollten deshalb lastabhängige Reaktanzen benutzt werden. Über eine Näherungslösung der Quasi-Poisson'schen Differentialgleichung werden die Streureaktanz des Feldes und die transienten Reaktanzen aus den Flußverkettungen abgeleitet. Als Beispiel wird ein Westinghouse Generator mit den folgenden Nenndaten nachgerechnet: 200 MVA, 15 kV, 50 Hz und 4 Pole. Die Ergebnisse der numerischen Analyse werden mit denen von konventionellen Berechngsmethoden verglichen.