ISSN:
1432-0487
Source:
Springer Online Journal Archives 1860-2000
Topics:
Electrical Engineering, Measurement and Control Technology
Description / Table of Contents:
Contents During ground faults in networks with isolated or compensated neutrals appear transient phenomena which are generally found to be of oscillating type. In this paper, the transients for networks with any number of lines are analyzed. Site tests, theoretical analysis and computer studies proved that in earth fault transients the following higher frequency components might be distinguished: discharge of faulty phase components, charge of sound phases components, inter-line compensating components. In this paper, formulae to calculate components and determine the phase currents and voltages are derived.
Notes:
Übersicht Beim Erdschluß in Netzen mit isoliertem Sternpunkt und induktiver Sternpunkterdung treten transiente Vorgänge auf, die meistens einen schwingenden Charakter haben, da das Netz ein System mit passiven Elementen L und C bildet. In der vorliegenden Arbeit wird eine Analyse dieser Vorgänge in Netzen mit einer größeren Anzahl von Leitungen dargestellt. Aus den theoretischen Überlegungen, der Analyse der Berechnungsergebnisse mittels eines Digitalrechners sowie aus den Untersuchungen bestehender Anlagen geht hervor, daß im transienten Erdschlußvorgang folgende freie Komponenten höherer Frequenz zu unterscheiden sind: - Entladungskomponenten der geerdeten Phase, - Nachladungskomponenten der Phasen ohne Erdung, - Ausgleichskomponenten zwischen den einzelnen Freileitungen und Kabeln der Schaltanlage. Im Beitrag werden die Abhängigkeiten zur Berechnung der Komponenten sowie der Phasenströme und-spannungen bei Erdschlüssen dargestellt.
Type of Medium:
Electronic Resource
URL:
http://dx.doi.org/10.1007/BF01407891