    Fire technology 22 (1986), S. 14-32 
    ISSN: 1572-8099
    Keywords: Computer facility ; fire loss ; fire protection ; halon ; smoke detectors ; VESDA ; nephelometer ; airflow effects ; spacing ; smoldering ; duct sampling ; pipework sampling
    Source: Springer Online Journal Archives 1860-2000
    Topics: Architecture, Civil Engineering, Surveying
    Notes: Abstract A recent fire in a computer center in Canberra, Australia, prompted an investigation of the installed smoke detection system. The opportunity was also taken to evaluate alternate detection equipment in the actual center under operational conditions. One device tested was VESDA, a new highly sensitive smoke detector developed in Australia for clean occupancies such as computer rooms and telephone exchanges. Details of the test program and the effects of high room airflows on all forms of detectors are presented. The effectiveness of VESDA in giving very early warning of fire is demonstrated.