On the application of Reynolds' analogy and the heat-exchange factor to the design of heat exchangers I

  • Published:
Flow, Turbulence and Combustion Aims and scope Submit manuscript

Summary

Part I. Reynolds' analogy between heat transfer and friction leads to the wellknown equationh=1/2fc pϱv. According to improved theories, for turbulent flow of gases in long straight ducts, the factor 1/2 is to be replaced byc=0.55 It is shown that for laminar flow in long ductsc is equal to 0.3 for a circular, and equal to 0.4 for a flat rectangular cross-section. Further in very short ducts an approximate theory is shown to give values that are of the same order of magnitude. Though the equationh=cfc pϱv has an approximative character, it has the advantage of being simple and generally valid for gases flowing in ducts. Applications and experimental data will be given in a subsequent article.