Contents The time patterns of short-circuit currents and therefore of the electromagnetic short-circuit forces in DC bus systems are very manifold; they only can be expressed by use of several parameters. For each of these patterns a substitute time function can be determined (rectangle or sinussquare) which causes about the same maximum instantaneous value of mechanical strength, like the original electromagnetic force, if the short-circuit duration is less than the half period of the mechanical oscillation. After suitable modification the rectangle function can also be used if the short-circuit duration is greater than the half period of the mechanical oscillation.
Notes:
Übersicht Die Zeitverläufe der Kurzschlußströme und daher auch der elektromagnetischen Kurzschlußkräfte in Gleichstromanlagen sind sehr vielfältig und können nur mit einer größeren Anzahl von Parametern beschrieben werden. Für jeden dieser Verläufe kann eine einfache Ersatzfunktion — Rechteck oder Sinusquadrat — bestimmt werden, die annähernd den gleichen maximalen Momentanwert der mechanischen Beanspruchung wie die ursprüngliche elektromagnetische Kraft verursacht, wenn die Kurzschlußdauer kleiner als die halbe mechanische Periodendauer ist. Nach geeigneter Modifikation kann das Ersatzrechteck auch dann verwendet werden, wenn die Kurzschlußdauer größer ist als die halbe mechanische Periodendauer.