Notes:
The results of applying the tentative, high temperature, International Standards Organization test methods DP 5925 Part 3, which was developed to measure smoke leakage of door assemblies during the course of a standard fire endurance test, are reported. A critical analysis reveals that the basic objective of the test method is limited in its utility in that fire scenarios in high-rise buildings may not be adequately simulated. Independent of this limitation, the analysis then identifies certain theoretical problems with the test method and its procedures. These lead to a conclusion that the test method is not generally reliable. An alternative test concept which appears to remove this limitation and all of its problems is described, and its development is advocated.