    Description: With high sensitivity and strong tolerance capability for the fault resistance, the fault component-based directional relay (FCBDR) has drawn considerable attention from industry and academia. However, the best application environment for FCBDR no longer exists when considering the large-scale connection of the doubly fed induction generator (DFIG)-based wind farms. Through a detailed analysis of the superimposed impedance of DFIG, this paper reveals that the performances of FCBDRs may be shown negatively impacted by the fault behaviors of DFIG when the crowbar protection inputs. In addition, this paper proposes a mitigation countermeasure to deal with those issues. The proposed countermeasure takes advantage of the different superimposed impedance features of DFIG compared with that of the synchronous generator (SG) to enhance the adaptability of the conventional FCBDRs. Extensive simulation results show that the proposed countermeasure can differentiate the fault direction clearly under different fault conditions.