Publication Date:
2018-10-31
Description:
A coordinated control method for doubly fed wind power generation system under unbalanced grid voltage is presented in this paper, which can remove the negative effects of unbalanced voltage on the doubly fed induction generator (DFIG) such as the unbalance of stator and rotor current. And the method can suppress the double frequency oscillations of the output active and reactive power. To improve the operating performance, the operation mechanism of DFIG system with a series grid side converter (SGSC) under unbalanced grid voltage is described firstly, and the strategy for series grid side converter aiming at maintaining the stator three phase voltage balance is proposed, and then the stator and rotor currents will keep balanced. Meanwhile, the mathematical model of the parallel grid side converter (PGSC) is analysed under unbalanced grid voltage and the double frequency power control equation is established. According to the control equation, a control strategy based on a prop...
Print ISSN:
1755-1307
Electronic ISSN:
1755-1315
Topics:
Geography
,
Geosciences
,
Physics
Permalink